The power circuit breaker e.industrial.ukm.1600s.1600.3p is designed to protect electrical installations from overload and short circuit in industrial and energy systems. It provides reliable switching of currents up to 1600 amperes with high mechanical and electrical durability.
Estimated Shipping


Quick Buy
Just 4 fields to fill in
Technical specifications
Article: i0010030
Number of poles: 3
Weight: 21.5 kg
Impulse withstand voltage (Uimp): 8 kV
Insulation voltage (Ui): 800 V
Application category: A
Terminal tightening force: 22.5 Nm
Rated operating voltage (Ue): AC 660 V
Current type: AC
Rated frequency: 50 Hz
Tripping setting at hp (Im): 5 In ±20%
Max. cross-section of connected wires: 40×10 mm²
Protection degree: housing – IP30, terminals – IP00
Compliance with standards: DSTU EN 60947-1; EN 60947-2
Disposal method: handover to a specialized company
Rated breaking capacity (Icu): 80 kA
Rated current (In): 1600 A
Mechanical/electrical durability: <2,500 / 500 cycles
Rated operational breaking capacity (Ics, AC 400 V): 40 kA
Operating temperature range: -25…+60 °C
Mounting: on a mounting panel
Altitude above sea level: ≤1000 m
Characteristics: thermomagnetic protection unit
Operating position: vertical and horizontal, with a deviation of ≤5°
Warranty: 12 months
Article: i0010030
Number of poles: 3
Weight: 21.5 kg
Impulse withstand voltage (Uimp): 8 kV
Insulation voltage (Ui): 800 V
Application category: A
Terminal tightening force: 22.5 Nm
Rated operating voltage (Ue): AC 660 V
Current type: AC
Rated frequency: 50 Hz
Tripping setting at hp (Im): 5 In ±20%
Max. cross-section of connected wires: 40×10 mm²
Protection degree: housing – IP30, terminals – IP00
Compliance with standards: DSTU EN 60947-1; EN 60947-2
Disposal method: handover to a specialized company
Rated breaking capacity (Icu): 80 kA
Rated current (In): 1600 A
Mechanical/electrical durability: <2,500 / 500 cycles
Rated operational breaking capacity (Ics, AC 400 V): 40 kA
Operating temperature range: -25…+60 °C
Mounting: on a mounting panel
Altitude above sea level: ≤1000 m
Characteristics: thermomagnetic protection unit
Operating position: vertical and horizontal, with a deviation of ≤5°